    Harmonics, in an electrical power system, are currents and voltages with frequencies
    that are integer multiples of the fundamental power frequency. That is, in a power
    system with a fundamental frequency of 60 Hz., the second harmonic is 120 Hz., the
    third harmonic is 180 Hz., etc., etc.

    Harmonic currents are created by non-linear loads that generate non- sinusoidal
    currents. Harmonic currents, acting in an Ohm's Law relationship with the source
    impedances, produce harmonic voltages.
    The harmonic currents and voltages produced by balanced, three phase, non-linear
    loads are positive sequence harmonics (phasors displaced by 120 degrees, with the
    same rotation as the fundamental frequency), and negative sequence harmonics
    (phasors displaced by 120 degrees, with a reversed rotation).
    However, harmonic currents and voltages produced by single phase, non- linear
    loads, which are connected phase to neutral in a three phase, four wire system, are
    third order, zero sequence harmonics (the third harmonic and its odd multiples - 3rd,
    9th, 15th, 21st, etc., etc., phasors displaced by zero degrees). These third order,
    zero sequence harmonic currents, unlike positive and negative sequence harmonic
    currents, do not cancel but add up arithmetically at the neutral bus.

    SOURCE OF THIRD ORDER, ZERO SEQUENCE HARMONICS
    High levels of third order, zero sequence harmonics are principally the by- product of
    switch mode power supply technology which is used in modern office equipment and
    lighting systems, and in virtually all other low power electronic devices. These power
    supplies are efficient, small, light weight and low cost, and are in all other respects,
    highly suited to their task.
    Electrically, the AC source voltage of these devices is rectified to DC voltage and
    then used to charge a large capacitor. In one half cycle the capacitor is charged to
    the average value of the voltage sine wave. The electronic equipment then draws
    current from the charged capacitor, to a regulated lower limit, to power the device's
    circuitry. Before reaching that lower limit, the capacitor is again recharged to the
    average value in the next half cycle of the sine wave. This process, which is repeated
    twice in each cycle, causes AC current to flow only during a portion of the AC voltage
    wave in abrupt pulses. During the rest of the wave, when the voltage is below the
    capacitor's residual, the capacitor draws no current.

    Equipment containing switch mode power supplies includes personal computers, mainframe terminals, printers,
    photocopiers, facsimile machines and electronic ballasts in fluorescent lighting fixtures. On average, the zero
    sequence (180 Hz.) current generated by these devices exceeds 80% of the fundamental (60 Hz.) current
    consumed. For example, a personal computer, which consumes 1.08 Amperes fundamental current, was found
    to generate 0.90 Amperes third order, zero sequence current (83% of the fundamental).
    In isolation, these rather small non-linear loads may seem insignificant. However, in the numbers found in today's
    modern offices and data centers, their impact may be costly and even dangerous.

    EFFECT OF THIRD ORDER, ZERO SEQUENCE HARMONICS
    Significant levels of third order, zero sequence harmonic current and voltage in a low voltage (i.e. 120/208V),
    three phase, four wire system will have a severe impact on both the power distribution system and the devices
    connected to it. In considering the extent of this power quality problem, it is important to understand that, unlike
    positive and negative sequence harmonics, zero sequence harmonics do not normally propagate into the higher
    voltage levels of the distribution system. They are contained within the low voltage distribution transformer and its
    secondary, four wire system.
    Depending upon the capacity and configuration of the distribution system, the presence of third order, zero
    sequence currents may include any or all of the following symptoms:

    •        High Neutral Current
    •        High Neutral to Ground Voltage (Common Mode Noise)
    •        High Peak Phase Current
    •        High Average Phase Current
    •        High Total Harmonic Distortion of the Current
    •        High Total Harmonic Distortion of the Voltage
    •        High Transformer Losses
    •        High System Losses
    •        Apparatus Overheating
    •        Low Power Factor
    •        Electronic Protective Device Malfunction
    •        High Telephone Interference Factor
    •        Increased Apparatus Vibration

    Ironically, the devices which create the third order, zero sequence harmonics may be the most sensitive to the
    problems they create. The performance of the switch mode power supply, in particular the charging of its
    capacitor, is critically dependent on the magnitude of the peak voltage. These voltage harmonics can cause "flat
    topping" of the voltage waveform or lowering of the peak voltage. In severe cases the computer may reset due to
    its own power supply's failure.

    THE SOLUTION - FINDING HARMONICS
    There are a number of practical steps that can be taken to confirm the presence of harmonics in the electrical
    power system. (The inclusion of these procedures in a predictive/preventive maintenance program is fundamental
    to assuring power quality.)

    1.        As a first step, tour the facility to determine the types of equipment that are connected to the low voltage
    system. If this inventory includes the types of office equipment listed earlier, or electronic ballasts, harmonics are
    likely present.

    2.        Locate the low voltage power transformers that feed these non-linear loads and check for excessive
    heating. Remember that the harmonics will increase the transformers' losses and cause them to overheat at loads
    below nameplate ratings.
    Third order, zero sequence harmonic currents may also result in the overloading of the transformers' neutral
    terminals. Neutral currents may exceed phase currents under these harmonic conditions.

    3.        Using "True-RMS" (root-mean-square or equivalent heating value) meters, measure the phase and neutral
    currents and the phase to neutral voltages at the low voltage power transformers' secondary terminals. Again,
    under zero sequence harmonic conditions the neutral currents will exceed the vector addition of the three phase
    currents. Under severe conditions, the neutral currents may substantially exceed phase currents under balanced
    conditions. These conditions give positive identification of a third order, zero sequence problem.
    If "Average Responding" meters are also available, further proof may be obtained by repeating the above tests
    and comparing the results. If the current and voltage waveforms are sinusoidal, the results of both measurements
    will be the same.
    Since "Average Responding" meters are only accurate under pure sine wave conditions, any distortion of the
    waveform will cause the "Average Responding" meter to read low. This reading may be as much as 50% lower
    than the "True-RMS" reading. By dividing the results of the "Average Reading" meter by the "True-RMS" meter,
    one may obtain an "A/R" Ratio. A ratio of 1 would indicate little or no distortion while 0.5 would indicate substantial
    harmonic distortion.

    4.        If harmonics are present at the power transformer, these same methods may be employed to measure the
    currents and voltages at each of the splitter boxes, feeder breakers and subpanels in the system. These
    additional measurements will help to locate the sources of the problem.

    5.        With high levels of third order, zero sequence harmonics in the system, there will be high levels of zero
    sequence, 180 Hz. current flowing in the neutral circuits. With the increased impedance of the neutral circuits at
    this frequency, and with single point grounding at the power transformers' neutral terminals, higher than normal
    neutral to ground voltages can be anticipated, particularly at the perimeter of the system. Conveniently, these 180
    Hz. voltages, which may be measured at branch circuit wall receptacles, are not entirely dependant on local loads.
    MEASURING HARMONICS
    In order to develop an engineered solution to this power quality problem, it is usually necessary to measure the
    harmonics using a harmonics analyzer. These measurements will provide detailed information on the full spectrum
    of harmonic currents and voltages, including:

    •        Total and individual harmonic distortions
    •        Fundamental and individual harmonic RMS voltages and currents
    •        Power flow for the fundamental and individual harmonics
    •        System impedances, including phase angles, for the fundamental and individual harmonics
    •        IT or kVT products for each individual harmonic
    •        Telephone interference factor (TIF)

    AN ENGINEERED SOLUTION
    Excessive third order, zero sequence harmonic currents, that occur in the neutrals of low voltage distribution
    systems in commercial buildings and data centers, first drew attention in the mid 1980s. Both the density of non-
    linear loads and the rapid increase of their use, previously unseen, introduced rather unique problems to which
    solutions did not really exist at the time.
    Today, a number of solutions have been proposed to address this phenomenon. Whether applied at the design
    stage or later when a problem is discovered in an existing installation, the basis of these recommendations has
    been to derate or oversize certain system elements, particularly the power transformer and the neutral
    conductors. These suggestions, unfortunately, may introduce a whole new set of problems - an increased fault
    withstand requirement and short circuit interrupting level.

    The most practical solution to this problem, however, is the removal of the zero sequence harmonic currents. One
    conventional solution is the application of an LC shunt filter tuned to the 3rd harmonic. This device, however, is
    case specific. If the harmonic current increases beyond the filter's design criteria, it will become overloaded. In this
    condition, capacitor fuses will interrupt and the filter's tuning will be shifted. In this condition the filter will not
    remove the desired harmonic current.

    Harmonic Filters have been developed to directly *cancel* harmonics in a power system. The Filter has the
    characteristics of an ideal zig-zag auto transformer with high positive and negative sequence impedance, ultra low
    zero sequence impedance, high Q (quality factor), low losses, at the fundamental frequency and all appropriate
    lower order harmonics.
    As with any harmonic mitigation technique, a detailed system study may be required in order to predict a result.
    Moreover, the misapplication of any device, intended to correct this problem, can have serious system
    implications. Geetech. offers ENGINEERED SOLUTIONS for the mitigation of all power system harmonics.
    The Harmonic Filter solution has no parallel in the industry and advances the engineering of power distribution.
    United Energy Associates' Harmonic Filter directly corrects the harmonic distortion problem providing high quality
    power for modern electronic machines and is guaranteed to work. Harmonic Filter solutions available for office
    buildings are designed to fit the facility's power system.

    THE BENEFITS:
    •        SHUNTS THIRD ORDER, ZERO SEQUENCE HARMONIC CURRENTS
    •        REDUCES NEUTRAL CURRENT
    •        SAFEGUARDS NEUTRAL CONDUCTOR
    •        IMPROVES SYSTEM PROTECTION
    •        REDUCES NEUTRAL TO GROUND VOLTAGE
    •        REDUCES PEAK PHASE CURRENT
    •        REDUCES AVERAGE PHASE CURRENT
    •        REDUCES TRANSFORMER OVERLOAD
    •        INCREASES SYSTEM CAPACITY
    •        REDUCES SYSTEM LOSSES
    •        REDUCES TOTAL HARMONIC DISTORTION
    •        IMPROVES POWER FACTOR OF NON-LINEAR LOADS
    •        IMPROVES PHASE CURRENT BALANCE
    •        IMPROVES PHASE VOLTAGE BALANCE
    •        CARRY THROUGH SINGLE PHASE OUTAGE
    •        INSTALLS WITHOUT SHUTDOWN
    •        STAND ALONE SOLUTION
    •        COST EFFECTIVE SOLUTION





    K-Factor Defined
    communications equipment, and other DC-powered loads) has created a major problem for specifying engineers,
    contractors and building owners. The non-linear nature of their switched-mode power supplies generate harmonic
    currents that cause transformers and system neutrals to overheat and destroy themselves.

    What is K-Factor?

    K-factor is a weighting of the harmonic load currents according to their effects on transformer heating, as derived
    from ANSI/IEEE C57.110. A K-factor of 1.0 indicates a linear load (no harmonics). The higher the K-factor, the
    greater the harmonic heating effects.

    When a non-linear load is supplied from a transformer, it is sometimes necessary to derate the transformer
    capacity to avoid overheating and subsequent insulation failure.
    The reason for this is that the increased eddy currents caused by the harmonics increase transformer losses and
    thus generate additional heat. Also, the RMS load current could be much higher than the kVA rating of the load
    would indicate.
    Hence, a transformer rated for the expected load will have insufficient capacity.
    The K-Factor is used by transformer manufacturers and their customers to adjust the load rating as a function of
    the harmonic currents caused by the load(s).

    Generally, only substation transformer manufacturers specify K-factor load de-rating for their products. So, for K-
    factors higher than 1, the maximum transformer load is de-rated.
    Some manufacturers, who produce both transformers and products like motors or ballasts, are sensitive to
    measuring K-factor since they know that poor K-factors of ballasts and motors will de-rate the maximum load their
    transformers can carry.  From the customer’s viewpoint, K-factor must be established in order to calculate the size
    of the transformer that is needed. In other words, if a company with many offices were to install poor quality
    electronic ballasts having a poor K-factor, a larger transformer would be needed than is apparent from the overall
    power consumption calculation